Category Archives: testing and verification

DWHR follow up

As I said in the last post, the primary benefit of running the DWHR performance test was the discovery that it wasn’t operating as intended. It gave me a chance to fix the problem and have the heat exchange and heat recovery process run at its full potential, which I measured at 46.7%.

DWHR-07

That in turn should help me save some money, which is important to make this investment pay off. There is a lot of copper in the DWHR, and it doesn’t come cheap. We bought ours for $617.00 a few years back.

DWHR-01

To sweeten the investment, Renewability provides an energy savings calculator on their website, to give the consumer an idea what level of savings could be expected.

Our DWHR (the R2-60 PowerPipe) serves the first floor and second floor bathroom showers. I assumed an average occupancy of 3 people per apartment, 0.75 showers per person per day and a shower time of five minutes. According to the energy savings calculator, we could expect annual savings of

  • 388,605 Btu (or 4.1 gigajoules),

which would translate into

  • $67.36 savings per year.

If I increase the shower time to 10 minutes, the expected annual savings increase to

  • 767,732 Btu (or 8.1 gigajoules),

which would translate into

  • $132.96 savings per year.

I guess the savings will lie somewhere in between the five and 10 minute shower time scenarios, and so will be the payback time for the DWHR, which would fall somewhere between four and a half to nine years.

That “M” word!

Using the calculator is not as straight forward as you may think – as I found out. First, it appeared to be down quite a lot, displaying an error message. This may just be a temporary issue, or so I hope.

Secondly, using the calculator, I was reminded that it is us (or should I say US) against the rest of the world. I think we must be the only culture left that doesn’t use the metric system. Canada does use the metric system (bless the Canadians!), and Renewability, the manufacturer of the DWHR, is a Canadian company.

The use of the metric system becomes relevant in the energy calculator if your fuel type is natural gas. The input field ‘Cost of Fuel’ uses the unit $/cubic meters natural gas – and not therms! A subtle detail that makes a difference in the calculator output.

How do you determine the cost of fuel?

And I am not talking about unit conversion – yet. Should I just use the cost per therm and ignore all the delivery charges and other add-ons?

I opted for what would I call the true cost. I added up the total volume of cubic feet of natural gas delivered over the past 12 months and converted it into cubic meters. I also added up the bill totals for the past 12 months and divided it by the total cubic meter volume. That gave me an average fuel cost of $0.55 per cubic meter of natural gas.

Closing comments

The $0.55 fuel cost is a snapshot. It is on a sliding scale depending on the occupancy of the building and natural gas prices.

I also have to take the calculator output at face value. I have not cross-checked the results through my own calculations. The fact that the advertised effectiveness of the DWHR was right on par with my own test results gives me some confidence into the energy savings calculator results.

Related posts:

DWHR performance test – good data

Although I would have liked a heat recovery rate of close to 90% for our drain water heat recovery (DWHR) unit, I knew that I couldn’t trust that number. Some good troubleshooting led us to the problem, thanks to some expert advice.

The pressure differential between the supply line to the domestic hot water tank and pre-heated water line from the DWHR prevented the setup from working properly, as did our less than perfect plumbing layout. Fortunately, we were able to resolve the issue with a quarter turn on a shut-off valve.

DWHR-13

Another test

It’s time to run the performance test once more to see if I could get some credible readings. I attached the temperature probes again to the three data points on the DWHR:

  • Cold potable water in (Tci)
  • Pre-heated potable water out (Tco)
  • Hot drain water in (Thi)

DWHR-09

As before, I took readings every 20 seconds while Cathy was taking a shower upstairs. Once I punched the readings into the spreadsheet, I saw some good data emerging.

The data

DWHR-07

The heat recovery rate for our PowerPipe R2-60 maxes out at 46.7%, which is a smidgen above the published performance rating of 46.1% by the manufacturer Renewability. Still, this took me by surprise.

I am somewhat suspicious of the performance ratings you find in product literature. Maybe the performance is inflated to help in selling the product. Maybe the laboratory test set up is so removed from the real world that test results don’t translate.

Yet, the DWHR results were right on the mark, as were the results for the ERV testing. Maybe I need to adjust my attitude?

The real value of the DWHR performance test was the discovery that the setup didn’t work as intended. I would have had pre-heated water sitting in the DWHR, doing a whole lot of nothing, whereas it should have fed into the domestic hot water storage tank. That could have gotten expensive, because next to no heat recovery translates into next to no savings!

Related posts:

Test results to dream of

Winter appears to be out of sight. But before it gets out of mind, let’s look at the performance of one of our heat recovery gadgets – the drain water heat recovery unit (DWHR).

DWHR-10

We installed this beauty in the basement, at the bottom of the sewer stack that drains the 1st and 2nd floor showers.

While I want to let the shower water go, I would love to keep the heat that is in that water. The DWHR allows me to recover and reuse a large chunk of that thermal energy.

Water running down a drain stack tends to cling to the pipe walls. While the hot drain water is running down the inner copper tube of the DWHR, it transfers its thermal energy to the cold potable water that is flowing up in the outer copper spirals, effectively pre-heating it.

DWHR-08

That is the theory. But what I really want to know is if the heat exchanger works as promised and what percentage of the thermal energy I actually recover. The technical term of what I measure is “effectiveness” or “empirical heat transfer rate.”

Testing the effectiveness of the DWHR is remarkably similar to that of the ERV. I look at three data points:

  1. Cold potable water in (Tci)
  2. Pre-heated potable water out (Tco)
  3. Hot drain water in (Thi)

DWHR-09

I attached my temperature probes to each data point at the DHWR unit and took readings every 20 seconds for 10 minutes while Cathy was taking a shower upstairs.

The results were excellent! Just by touching the outer coil, I could feel how the cold inlet water water got increasingly hot toward the top outlet (Tco). Once I had punched the numbers into my spreadsheet, I came close to 90% effectiveness (or a 90% heat recovery rate).

But therein lies the problem: If it sounds too good to be true…

A quick web search will tell you that the effectiveness of DWHR units typically ranges from 40% for smaller units to 70% for the largest units. Plus, the in-house test data by Renewability for my DWHR (called the R2-60) is listed at 46.1%.

Something is amiss and I would like to find out what it is.

Related posts:

That heat is mine, and I plan to keep it!

DWHR installation

ERV performance test

Blower door test – before insulation

I mentioned the blower door test, which is one of the insulation rebate requirements. To quantify the energy savings we need to conduct one blower door test prior and one after the insulation installation.

What is a blower door test?

A blower door test depressurizes the building (typically to 50 pascal) and measures the resulting air flow in and out of the building. This test establishes how air tight a building is, and/or allows the detection of air leaks that need to be fixed.

Why do air leaks or air tightness matter? Because unwanted air movement can significantly negate the effect of insulation. The classic example is batt insulation in a stud wall. If cold or hot air can blow through the insulation batts, they have little insulation value.

Depressurizing the building sounds complicated, but is relatively straight forward. It starts with an adjustable metal frame that can be fitted into a door, typically the front or back door. Before the fitting, the frame gets wrapped into a cover, which has a hole toward the bottom for a powerful fan that will take care of the depressurizing.

Measuring the pressure differentials and air leakage is a little more complicated. It requires a sophisticated pressure and flow gauge which is mounted on the inside of the blower door, and a few tubes.

You may have noticed in the video above the small green tube that John placed on the front porch and through the fan opening. That tube references the pressure outside the building and connects to the gauge, which at the same time measures the pressure inside the building.

To measure the airflow, the gauge measures again the pressure inside the building and references it against the pressure inside the fan, which is connected to the gauge with a small red tube.

Conducting the test

We were almost ready to go, except for a few more items that needed to be checked:

  • Close all windows and exterior doors (except the one with the blower door).
  • Install all deadbolts and door knobs in exterior doors, or seal over them (in our case, the back door leading to the porch).
  • Seal all ventilation terminals (HRV and range hood).
  • Fill all dry P-traps with water – sinks, showers, floor drains, etc.
  • Seal any conduits connecting the basement and first floor to the second floor.
  • Turn off heating equipment or water heaters (did not apply here as the heating equipment is located in the basement, not the 2nd floor, which we were testing).

One note on the numbers shown on the pressure and flow gauge: The number to the left shows the pressure reading (in pascal), and the number on the right shows the airflow in cubic feet per minute (cfm).

The first test results

Our official reading for the 2nd floor was 4,763 cfm at 50 pascal (4,763 cfm50).

Another metric that is used is air changes per hour at 50 pascal (ach50). To convert to an ach50 value, I multiply the cfm50 reading by 60 (60 minutes) and divide the result by the building volume (20,608 cubic feet for the second floor).

4,763 cfm50 * 60 minutes / 20,608 cubic feet = 13.9 ach50

In translation: While the 2nd floor is depressurized to 50 pascal, its entire air volume is exchanged almost 14 times per hour.

4,763 cfm50 or 13.9 ach50 appear to be high numbers but are not that uncommon for old buildings like ours. Here is what John from Chicago Home Performance, who did the blower door test, had to say:

Your house actually falls right in line with what I would expect with masonry buildings of similar construction type/age. I would say 7-15 ach50 is pretty normal depending on what has been done to the building over time. However, I have seen them as high as 20 ach50 in some really beat up places.

We have a pretty leaky 2nd floor. In fact, while we ran the blower door test, I walked around, felt the drafts and could easily follow them to their source. Take the unsealed gap between the 1st and 2nd floor for example…

… or the old double hung windows in the south wall.

Areas like this need serious air sealing. Some, like the old window, were sealed when we installed the replacement windows, while others, like the floor gap, wait for the closed cell SPF (spray polyurethane foam) application.

To learn more about blower door tests, visit the GreenBuildingAdvisor.com blog: Blower Door Basics.