On the hunt for a rational explanation for boiler lockout, I sunk my teeth into the pumps – believing that the system (main) pump for the hydronic heating system wasn’t running.
The pump status indicator on the Trinity LX 150 boiler touch screen didn’t correspond to what pumps were actually running. Even the pump diagnostic test only got one pump fired up, the boiler pump. I was convinced that I was onto something and called my ever patient installer, Mariusz.
He gave me a very simple task: “Look at how the pumps are wired.”
- The pump for the domestic hot water (DHW) loop was wired into a switch relay.
- The boiler pump was wired into the boiler.
- The system (or main) pump for the hydronic heating system also was wired into the switch relay.
“That is why you only have one pump [the boiler pump] running when you execute the pump diagnostic test, because that is the only pump controlled by the boiler”.
Mariusz asked me to bridge the zone wires, which is equivalent to the zone thermostat coming on. He said that at the same time, I should check the system pump load wire for current. I detected current and was able to conclude that the system pump was running just fine.
Last but not least, I checked the DHW pump, which was a lot simpler. We just let the hot water in the bathroom run. Once the temperature in the DHW tank started dropping, the DHW pump came on to reheat the tank.
In short, there was nothing wrong with the pumps.
The boiler has been running fine since the lockout. No further error messages. May be its time to lock out my own self – no more access to the boiler room, or at least the boiler touch screen.