Tag Archives: air sealing

How was that possible?

A couple of years back, after all major air sealing, we had a blower door test result of 2.1 ACH @ 50 pascal. This February the results dropped to 0.62 ACH @ 50 pascal in a follow up test! How was that possible?

From what I have read and heard, once the major air sealing is completed, it becomes increasingly difficult to tease out additional improvements in the blower door test results. And a drop from 2.1 to 0.62 ACH @ 50 pascal is – well – a massive improvement.

Let’s start by looking at what I mean by…

Major air sealing

In one sentence: We took good care of the building envelope.

On the 1st floor we had an application of closed cell foam followed by a layer of open cell foam. The 2nd floor just got one layer of closed cell foam. The closed cell foam on both floors was acting as our air barrier across the masonry wall plane.

The closed cell foam only provides a functioning air barrier if it is diligently installed. On a sloppy spray job, you may have to contend with leaks in your air barrier. I point to some examples here: on the open cell job on our 1st floor.

We air sealed the top of the attic with drywall, which was taped and mudded. The gaps around the attic edges were sealed with another bead of foam.

All penetrations through the building envelope were diligently sealed, typically with foam. Examples are:

  • The ERV fresh air intake and exhaust
  • The range hood exhaust
  • Any electrical conduits leading to the exterior
  • Any low voltage conduits leading to the exterior
  • The supply and return lines to our minisplits
  • Etc.

You can seal around electrical conduits, but that still leaves with a big hole – the conduit itself. To plug the conduit, we diligently used duct putty.

I made sure we had decent weather stripping on our exterior doors. And then there were the windows. We had good quality replacement windows on the 1st floor, while the 2nd floor still had the old double hung vinyl windows. However, I made sure the perimeter of each window was properly sealed.

This was our baseline that gave us the blower door test result of 2.1 ACH @ 50 pascal. Now let’s take a look at what may have caused the drop to 0.62 ACH @ 50 pascal.

The 1st floor

I took a mental walk through all improvements on the 1st floor, major or minor, since we completed the major air sealing.

There was some additional air sealing on the kitchen back door. This is a fancy way of saying, “I installed some additional weather stripping.” The back door was pretty air tight to begin with, though, so I am not sure that this effort contributed that much.

There was the transom window over the kitchen back door. It had a temporary window that most likely was not properly air sealed. I didn’t replace it with a properly sized window until I ordered the replacement windows for the 2nd floor last fall. This should have contributed to the reduction in air leakage.

 

I suspect that the biggest impact lies with the air sealing work I did on the 1st floor casement windows. Regular readers may recall my air leakage problems in the corners of the casements. The manufacturer was not able to resolve the issue, but was gracious enough to refund me the money for the leaky windows.

As described in a past post, the problem came down to 1/16 inch and I was determined to plug that gap. I invested a little research time online and found a single coated, low density, PVC foam tape, 1/16 inch thick. I installed it on the operable part of the casement, right across from the gaskets on the casement frame. The foam tape pushed against the gaskets, closed the gaps, and eliminated the air leaks. I could tell it did, because the cold drafts on windy winter days disappeared.

 

 

2nd floor

Like on the 1st floor, I did some additional air sealing around the 2nd floor back door. The most significant improvement may have come from my work on the door threshold, which was not properly sealed.

But the biggest reduction in air leaks must have come from the 2nd floor replacement windows, which I installed last fall. I thought I had done a good job air sealing the old double hung windows after we finished with the spray foam installation, but the blower door test numbers tell me otherwise.

Conclusion

I clearly underestimated the amount of air leakage from the 1st floor casement windows and the effect of good quality replacement windows on the 2nd floor. Or, I overestimated the effect of my air sealing efforts on those old double hung windows.

The more I think about it, the more I am convinced that the windows were the major contributors to the drop from 2.1 to 0.62 ACH @ 50 pascal.

So, maybe it is not that difficult to improve your blower door results after all major air sealing after all! Or maybe I have a unique definition of what “major air sealing” means.

And here is another thought: I made it my job throughout our deep energy retrofit to stay on top of all air sealing efforts and moisture management issues. That was my responsibility. There was no hole in the building envelope I didn’t know about or I didn’t make sure was sealed properly.

Most other remodels, gut-rehabs, energy retrofits, or even new construction that follow conventional methods probably won’t have that one person who is in charge of tracking the air sealing. There are a number of contractors and tradespeople coming and going, all doing their own thing, but no one person has a real incentive to pay attention to details – sometimes not even the details of their own work. Air sealing is probably not on their mind, or may not even be a concept to some.

Usually there is the general contractor, who, one could assume, would be in charge of managing all contractors and tradespeople and making sure air sealing is tracked and accounted for. But the success stories seem to be more an exception than the rule.

Building green has an uphill battle ahead with a lack of skilled labor, with contractors that often don’t think an inch beyond their own trade, and with no one on the job site who is responsible for tracking air sealing from the planning stages to the final execution.

Related posts:

A magic 0.6 – as airtight as it gets

Reaching a major milestone is a reason to celebrate. But what do you do when you exceed all expectations and it takes you by surprise?

Old buildings like ours are notoriously leaky. Even a lot of newer buildings are. That’s something you will notice when you try to escape the cold drafts in your own home on a windy winter day. We know how leaky our building was before we started with the deep energy retrofit, because we conducted a blower door test on the 2nd floor unit. It leaked a whopping 4,763 cfm @ 50 pascal.

The blower door basically depressurizes the building or unit by 50 pascal. At that point you take a reading of the airflow. In our case, the 4,763 cfm @ 50 pascal is the air volume that is leaking through the building or unit. To get to a metric that has a common denominator, the airflow is converted into air exchanges per hour or ACH @ 50 pascal. We ended up with 13.9 ACH @ 50 pascal.

Our results were not that unusual. Blower door test results often range from 7 – 15 ACH @ 50 pascal, depending on the building.

What are the air leakage standards?

Air leakage standards in the U.S. are a moving target. There is no national standard; instead, a builder or homeowner can pick from a list of requirements. Here are some examples:

The PHIUS standard discontinued to use the metric of air exchanges per hour (ACH), and instead replaced it with cubic feet per minute (cfm) of air infiltration per square foot of gross building envelope area, measured at 50 and 75 pascal. The rationale behind this metric is that it can be scaled, unlike ACH. Because ACH is based on the building volume, it allows larger buildings to have a greater rate of air leakage compared to smaller buildings. And where do air leaks occur? At the surface of the building enclosure. Thus it appears logical to measure air leakage based on the gross building envelope area.

How did we do?

We ran a blower door test on the 2nd floor unit after we finished with the spray foam insulation and major air sealing. The results were 720 cfm @ 50 pascal or 2.1 ACH @ 50 pascal. That was a remarkable improvement over the 13.9 ACH @ 50 pascal and caused some excitement.

About a year later we conducted a blower door test on the finished 1st floor unit during a project tour organized by the Chicago Community Loan Fund.That test gave us a reading of 630 cfm @ 50 pascal which also equated 2.1 ACH @ 50 pascal.

 

I have learned over the past years through reading and talking with green builders that once the major air sealing is done, shaving the last few 1/10th off an ACH @ 50 pascal is painstaking work. It involves a lot of chasing, tracking and sealing small air leaks.

All our major air sealing work was completed. My hope was that I would be able to get a final result of just under 2 ACH @ 50 pascal by plugging the last few leaks I could find. That would have made me very happy!

In for a major surprise…

This past week, I hosted another tour of our deep energy retrofit. It was organized by Eco Achievers, our LEED rater and also a PHIUS+ Rater. Part of the tour was another blower door test demonstration. This time we tested the 1st and 2nd floor unit together.

 

The reading of 385 cfm @ 50 pascal seemed unreal. So much so that I asked to start the test over again including another recalibration of the blower door equipment. Yet we got the same reading for a second time.

385 cfm @ 50 pascal for the 1st and 2nd floor unit equates 0.62 ACH @ 50 pascal! If I use the PHIUS metric, I come up with 0.05 cfm50 per square foot of gross envelope area.

Do I need to say that it took a while for this to sink in? Never in my wildest dreams would I have thought a less than or equal to 1 ACH @ 50 pascals would be possible on our deep energy retrofit. I guess it’s time to celebrate! And I have to find out how I managed to drop from 2.1 to 0.62 ACH @ 50 pascal.

Related posts:

Porch enclosure – stair insulation

I am obsessed with insulation. And in case you haven’t noticed, let me tell you about the stair insulation in the back porch. The perfect hybrid between ceiling and wall insulation: a combination of cut-and-cobble and some fluffy rock wool.

To address the air sealing, I again had to rely on cut-and-cobble pieces of XPS insulation underneath the stairs. And like with the ceiling, I carefully foamed around and between the pieces.

Back-porch-52 Back-porch-53

I had the idea of filling the space between the installed XPS and the bottom of the stair stringer with rock wool. Our rock wool batts that typically are installed in a framed wall were not really suitable here. But I found several bags of loose rock wool at my favorite gold mine, the Rebuilding Exchange.

Back-porch-54

To find a way around gravity, and to add an extra layer of insulation, I attached another sheet of XPS insulation to the bottom of the stair stringers. That allowed me to stuff the space with the loose rock wool without it falling down.

Back-porch-55 Back-porch-56Back-porch-57 Back-porch-58

Well, with that done, I can start to think about drywall and painting!

Related posts:

Porch enclosure – wall insulation

I knew where I was going with the wall insulation – I had sketched it out when I was planning for the porch enclosure.

back-porch-28 back-porch-30

I had room for a double stud wall using standard two by fours. The 1st half (outer part) of the double stud was as already in place. I installed it when I put up the exterior sheathing. This wall was ready to receive the rock wool insulation.

Back-porch-48 Back-porch-49

With the 1st half (outer part) of the wall completed, I could start framing out the 2nd half (inner part). To minimize thermal bridging, the studs from the 1st and 2nd half are offset from each other.

Back-porch-50

The two layers of rock wool alone (one layer for each half of the double stud wall) add up to a R-value of 30. With an additional one inch layer of XPS insulation on the outside, the R-value climbs to R-35.

Back-porch-51

I am often asked why I opted for rock wool and not the cheaper fiberglass insulation. Well, rock wool insulation is easy to cut, shape, and install. It allows one to fill all nooks and crevices, like spaces behind electrical boxes.

But more importantly, I consider rock wool a low cost fire insurance. Again, rock wool is made out of rocks. And rocks don’t burn!

Related posts:

Porch enclosure – ceiling insulation

It doesn’t need to be cozy (at least not all the time), but it shouldn’t be freezing. That would be the expectation for the workshop and storage in the enclosed basement portion of the back porch.

To get there with the minimal amount of space conditioning, we need a fairly decent amount of insulation with an airtight enclosure. I got the walls airtight through careful caulking of the XPS insulation and exterior sheathing. I now had to turn my attention to the ceiling.

back-porch-42

Cut-and-cobble

If you follow the online musings of green building and energy geeks, you will have heard of cut-and-cobble. It is declared counterproductive by some, ridiculed by others, yet beloved by tinkerers. And sometimes it is simply an option that makes sense, like in our case.

Cut-and-cobble is the process of taking XPS or ISO insulation and cut it into strips to fit it (or cobble it) in between the floor joists. But cut-and-cobble alone does not provide an airtight assembly. It takes some canned spray foam (or caulk) to fill all the gaps between the insulation and framing and abutting insulation pieces. And yes – it can be tedious. Thus the different opinions on this process.

Back-porch-43

To start with the ceiling insulation I used salvaged two inch thick XPS boards. The key to facilitate the foaming around the edges, is to leave a ? inch gap all the way around. That gap makes it easy to insert the straw from the foam can and get it filled to the full depth of two inches.

Back-porch-44

Cut-and-cobble is also an excellent way to use up scraps. And I had plenty of four inch XPS scraps from our 2nd floor ceiling-gone-wrong. These scrap pieces were turned into the the 2nd layer of insulation, and this time I fit them tightly between the joists.

Back-porch-45 Back-porch-46

I had filled six inches of the nine and a half inches between the joists with insulation. The remaining three and a half inches were lending themselves perfectly to rock wool insulation.

Back-porch-47

Another rationale was that the rock wool also acts as a fire wall. Remember – rocks don’t burn.